Сучасні протоколи передачі шкали часу інтелектуальних електроенергетичних систем зі зниженою аварійністю

Автор(и)

  • О. М. Величко
  • В. В. Коваль
  • О. В. Самков
  • І. Ю. Шкляревський

Анотація

UDC 681.516.75:631.234

TIME-SCALE DISTRIBUTION MODERN PROTOCOLS FOR SMART GRID POWER SYSTEMS WITH LOW ACCIDENT RATE

O. Velychko, V. Koval, O. Samkov, I. Shkliarevskyi

 

In the last about 10 years , in different counties the reasons for power failures or blackouts in which more than one power utility is involved must be analyzed. The so-called cascading emergency power outages, which entail serious social consequences (emergency stops of trains in underground tunnels, trams and trolleybuses streets, elevators in high-rise buildings, disconnect from the electric power electrical devices, hospitals, kindergartens , enterprises with continuous production, etc.) have appeared for the general public. Examples of  some power outgates are shown in the Table 1.

 

Table 1.

Year

Country or region

Involved population , millions

2003

USA, Canada

55

2003

Italy

56

2005

Indonesia

100

2005

Russia

3

2011

USA, Mexico

5

2012

India

620

 

The North American Blackout back in August 2003 visualized how painful and time consuming it can be to align data, whose time stamps are derived from inaccurate time references. As a result the task force investigating the blackout demanded a regulation that ensures a minimum absolute accuracy for time stamped disturbance event data.

Analysis of cascading outages of electricity, which recently took place in the world [1],[2] can show, in addition to the purely technical, the presence of other, more common causes of such events. First of all, it's deregulation of the electricity market, making this market extremely highly, but less manageable. In order to prevent undesirable consequences specified problematic situation in the energy sector developed the concept of intellectual power grid (Smart Grid), which is an important part of that is associated with continuous monitoring of grid stability parameters linked to real-time with microsecond precision.

In Ukraine there is a public service Time and Frequencies Reference for coordination and implementation of activities aimed ensuring the uniformity of time and frequency measurements, creating and maintaining a national time-scale confirmed to the best national scales the world. But Ukraine's existing time and frequency distribution technical means and methods do not form a single system and can not meet the requirements of all customers time-frequency information that encourages them to use synchro-information from other states’ sources (GPS or GLONASS), which threatens the national security and increases the risks of loss of traceability time and frequency within the state. Implementation of the Precision Time Protocol (PTP), defined in the IEEE 1588 standard provides a very accurate and safe way to distribute time references throughout the power station’s Ethernet networks. PTP allows distributing reference time information in a local area network like NTP does, but due to the innovative protocol it allows to reach accuracies in the sub-microsecond range.

There’s a PTP supporting equipment named SU-1588, developed and manufactured in Ukraine, which provides the necessary services distributing the national time-scale from the Secondary Time and Frequency Reference located in Ukrmetrteststandart enterprise in Kiev. The direct connection 30 minutes interval stability between different manufacturers’ equipment was tested in [4]. Table 2 shows some results from [4] combining with some SU-1588 results  provided by it’s manufacturer. 

Table 2.

    Slave/

Master       

Slave A

Slave B

Slave C

Slave F

SU-1588S

(slave)

Information source

Master A

-

705

304

798

-

[4]

Master C

715

156

-

43

-

[4]

Master D

670

255

232

200

-

[4]

OSA-5535

-

-

-

-

320

IST Ltd

SU-1588M

-

-

-

-

250

IST Ltd

 

Conclusion

A modern power field needs precise time-stamping for new monitoring and measurement methods for Smart Grid’s implementation. The SU-1588 equipment supporting “power” profile of IEEE 1588 protocol, is able to provide time-scale microseconds level distribution for power industry.

 

Посилання

Смирнов С. О. Причины возникновения и меры противодействия крупным авариям в электроэнергетических системах // ?звестия Коми научного центра УРО РАН / С. О. Смирнов, М. ?. Успенский. – Вып. № 1 (9), 2012. – С. 68–77.

Martinez E.V., et al. «Smart Grids. Part 1: Instrumentation Challenges», IEEE Instrumentation & Measurement Magazine, February, 2015, pp. 6–9.

Baumgartner B., Riesch C., Rudigier M., “IEEE 1588/PTP: The Future of Time Synchronization in the Electric Power Industry”, PAC World Conference 2012, Budapest, Hungary, 2012.

IEEE Instrumentation and Measurement Society, IEEE Std 1588™-2008 - Standard for a Precision Clock Synchronization Protocol for Networked Measurement and Control Systems, 2008.

Konovalov G., Kostik B., Koval V., Shkliarevskyi I. "Timing information's 24х7 monitoring as an important factor of network synchronization quality support", 2013 International IEEE Symposium on Precision Clock Synchronization for Measurement Control and Communication (ISPCS-2013), Digital Object Identifier: 10.1109/ISPCS.2013.6644769. 22-27 вересня, Лемго, Германия. 2013. – С. 89–94.

Estrela P.V., Bonebakker L., “Challeges deploying PTPv2 in a Global Financial company”, in Proc. IEEE ISPCS, San Francisco, California, USA, Sept. 23th–28th, 2012, pp. 25–30.

Концепція національної системи розповсюдження синхроінформації : зб. матеріалів Міжнародної науково-практичної конференції «Глобальні та регіональні проблеми інформатизації в суспільстві та природокористуванні ’2014», 26–27 червня 2014 р., НУБіП України / О. М. Величко, М. В. Головня, В. В. Коваль, І. Ю. Шкляревський. – К. : АграрМедіаГруп, 2014. – С. 22–23.

Сучасні технології синхроінформаційного забезпечення на основі протоколу прецизійного часу стандарту IEEE-1588 : матеріали III Міжнар. наук.-техн. конф. «Сучасні інформаційно-комунікаційні технології», м. Київ 17–20 листопада 2015 р. Т.ІІ Актуальні питання побудови сучасних телекомунікаційних систем і мереж / О. М. Величко, В. В. Коваль, В. П. Лисенко [та ін.]. – К., 2015. – С. 9–11.

Величко О. Н. Вторичный эталон единиц времени и частоты как источник сигналов синхронизации и времени / О. Н. Величко, М. В. Головня // Электросвязь, 2013. – № 2. – С. 22–25.

Shkliarevskyi I., «Precision Time Protocol in different applications: profile comparative analysis», T-Comm, v.8, #11, 2014, pp. 116–120.

IEEE C37.238-2011 IEEE Standard Profile for Use of IEEE 1588 Precision Time Protocol in Power System Applications, 2011.

Ingram D.M., et al., “Perfomance Analysis of PTP Components for IEC 61850 Process Bus Applications”, IEEE Transactions on Instrumentation and Measurement, vol. 62, No 4, April 2013, pp. 710–719.

Завантаження

Опубліковано

2017-02-24

Номер

Розділ

Статті