Експериментальні дослідження процесу термічного ураження залізобетонних опор струмами однофазного замикання на землю
Анотація
EXPERIMENTAL STUDY OF THERMAL SHOCK OF REINFORCED CONCRETE PILLARS BY CURRENTS SINGLE-PHASE GROUND FAULT
- A. Kvitsynskyy, O. Shelimanova, V. Santossky
In length, 10 kV air lines (AL) in rural areas on reinforced concrete pillars with ultrasonic currents up to10 Aexceed the length of allALsubstrates with a voltage of more than 1 kV. The neutral grounding of such electrical networks is one of the issues discussed during the last 10 to 15 years. The permissible duration of single-phase earth faults (SEF) in networks with isolated neutral and grounding currents up to10 Ain post-Soviet countries is not established.
The purpose of the research - depending on the ground resistance and current strength of the ultrasound to normalize the permissible duration of the regime of ultrasound, which does not violate the thermal stability of the supports.
The research was carried out by the staff of the UkrSilEnergoProject Institute.
According to our research, the minimum initial power from which the process of thermal damage to the underground part of the reinforced concrete support in the networks of 6 - 20 kV can begin and continue in the future, is:
1,5 - 1,8 kW - in case of support in soils with ρz ≤ 50 Ом ∙ m (chernozems with a humidity of 16%);
4,5 - 5,0 kW - in the case of support in soils with ρz - from 1000 ohm ∙ m to 1500 Ω m (sand with humidity 3 - 4%).
Conclusions
1. The isolated neutral of the 6-20 kV network with the currents of the SEF to10 Ashould not be grounded through a high-resistance resistor if the network has air lines on reinforced concrete supports with installed pins and supports, whose resistance is not normalized, and provided with natural conductivity underground part of the support.
2. For networks 6 - 20 kV it is necessary to develop guidance documents for the determination of the permissible time of existence of the SEF to prevent the thermal damage of the underground part of the support.
3. In networks of 20 kV, capacitive currents compensation should be used starting from 5 amperes and the limitation of the lifetime of the SEF for four hours.
4. Inorder to reduce the number of cases of ultrasound in the intermediate supports of a 20 kV overhead line, rod insulators shall be installed, and anchor-pendant on anchors.
Посилання
Kvitsynskyi, A. O., Shelimanova, O. V. (2016). Rozrakhunok protsesu termichnoho urazhennia zalizobetonnykh opor strumamy odnofaznoho zamykannia na zemliu [Calculation of thermal shock of reinforced concrete pillars by currents single-phase ground fault]. Naukovyi visnyk NUBiP Ukrainy, 242, 204–210.
HKD 34.20.507-2003 Tekhnichna ekspluatatsiia elektrychnykh stantsii i merezh. Pravyla (2006). [Technical operation of electric power stations and networks. Rules]. Kharkiv: Fort, 536.
##submission.downloads##
Опубліковано
Номер
Розділ
Ліцензія
Стосунки між правовласниками і користувачами регулюються на умовах ліцензії Creative Commons Із Зазначенням Авторства – Некомерційна – Поширення На Тих Самих Умовах 4.0 Міжнародна (CC BY-NC-SA 4.0):https://creativecommons.org/licenses/by-nc-sa/4.0/deed.uk
Автори, які публікуються у цьому журналі, погоджуються з наступними умовами:
- Автори залишають за собою право на авторство своєї роботи та передають журналу право першої публікації цієї роботи на умовах ліцензії Creative Commons Attribution License, котра дозволяє іншим особам вільно розповсюджувати опубліковану роботу з обов'язковим посиланням на авторів оригінальної роботи та першу публікацію роботи у цьому журналі.
- Автори мають право укладати самостійні додаткові угоди щодо неексклюзивного розповсюдження роботи у тому вигляді, в якому вона була опублікована цим журналом (наприклад, розміщувати роботу в електронному сховищі установи або публікувати у складі монографії), за умови збереження посилання на першу публікацію роботи у цьому журналі.
- Політика журналу дозволяє і заохочує розміщення авторами в мережі Інтернет (наприклад, у сховищах установ або на особистих веб-сайтах) рукопису роботи, як до подання цього рукопису до редакції, так і під час його редакційного опрацювання, оскільки це сприяє виникненню продуктивної наукової дискусії та позитивно позначається на оперативності та динаміці цитування опублікованої роботи (див.The Effect of Open Access).