Study of resonance phenomena when connecting 0.38 kv batteries of transverse compensation capacitors to the network
DOI:
https://doi.org/10.31548/energiya1(65).2023.042Abstract
The article deals with the operation of capacitor banks as part of regulated capacitor units connected to the 0.38 kV electrical network of power transformers of 10/0.4 kV consumer substations. It is known that capacitor banks are used to compensate for the reactive power of electrical receivers and equalize the load of phases in three-phase four-wire networks of 0.30 kV by creating reverse sequence currents equal in magnitude, but rotated by 1800 relative to the load currents due to the inclusion of a different number of capacitors between the network phases.
The wide presence of non-linear electrical receivers in electric networks causes the occurrence of higher harmonic components of voltage and current, which cause an increase in the current in capacitors, since the reactive resistance of capacitors decreases with increasing frequency. At the same time as the current in the capacitors increases, which can be regulated with the help of constructive measures, in unfavorable cases resonance phenomena may occur in the networks. Widespread use of capacitor banks creates risks of resonance of voltages and currents both at the main frequency of three-phase alternating current of 50 Hz and at frequencies of 150, 250, 350 and 550 Hz due to higher harmonic components of voltage and current.
The obtained results indicate that for the resonance of currents to occur at the main frequency for power transformers of different capacities, the power of the capacitor banks should be from 0.02 kV×Ar per 1 kV×A of power (for a 630 kV×A transformer) to 0.034 kV×Ar (for a 25 kV×A transformer), and for the occurrence of voltage resonance, respectively, from 18.7 kV×Ar/kV×A to 26 kV×Ar/kV×A.
In addition, calculations show that to increase the power factor even by a small amount (from 0.9 to 0.95), it is necessary to install capacitor banks of at least 0.14 kV×Ar/kV×A, and to increase the power factor from 0, 7 to 0.95 - only 0.66 kV×Ar/kV×A.
Key words: capacitor batteries, power transformers, capacity, inductance, resonance of voltages and currents, Q-factor of the circuit
References
Metodyky obchyslennia platy za peretikannia reaktyvnoi elektroenerhii, zatverdzhenoi Nakazom Minenerhetyky ta vuhilnoi promyslovosti Ukrainy vid 06.02.2018r №87 [Methods of calculating the fee for the flow of reactive electricity]. Kyiv: Ob’iednannia haluzevykh pidpryiemstv «HRIFRE», 2018. 20.
Boiko, V. S., Boiko, V. V., Vodoliub, Yu. F. (2004). Teoretychni osnovy elektrotekhniky [Theoretical foundations of electrical engineering]. Kyiv: Politekhnika, Vol. 1, 272.
Omelchuk, A. O. (2016). Enerhozberihaiuchi rezhymy v systemakh elektropostachannia [Energy-saving modes in power supply systems]. Kyiv: TsP «KOMPRYNT», 257.
SOU – N MPE 40.1.20.510.:2006. Metodyka vyznachennia ekonomichno dotsilnykh obsiahiv kompensatsii reaktyvnoi enerhii, yaka peretikaie mizh elektrychnymy merezhamy elektroperedavalnoi orhanizatsii ta spozhyvacha [Methodology for determining economically feasible amounts of compensation for reactive energy that flows between the electric networks of the power transmission organization and the consumer]. Minpalyvenerho, nakaz № 1 vid 05.01.2006.
Pravyla ulashtuvannia elektroustanovok [Rules for arranging electrical installations] (2017). Kharkiv: Fort,. 760.
Downloads
Published
Issue
Section
License
Relationship between right holders and users shall be governed by the terms of the license Creative Commons Attribution – non-commercial – Distribution On Same Conditions 4.0 international (CC BY-NC-SA 4.0):https://creativecommons.org/licenses/by-nc-sa/4.0/deed.uk
Authors who publish with this journal agree to the following terms:
- Authors retain copyright and grant the journal right of first publication with the work simultaneously licensed under a Creative Commons Attribution License that allows others to share the work with an acknowledgement of the work's authorship and initial publication in this journal.
- Authors are able to enter into separate, additional contractual arrangements for the non-exclusive distribution of the journal's published version of the work (e.g., post it to an institutional repository or publish it in a book), with an acknowledgement of its initial publication in this journal.
- Authors are permitted and encouraged to post their work online (e.g., in institutional repositories or on their website) prior to and during the submission process, as it can lead to productive exchanges, as well as earlier and greater citation of published work (See The Effect of Open Access).