Diagnosis of the condition high-voltage support insulators by leakage currents

Authors

  • A. Kotysh Central Ukrainian National Technical University image/svg+xml
  • K. Petrova Central Ukrainian National Technical University image/svg+xml
  • I. Savelenko Central Ukrainian National Technical University image/svg+xml
  • S. Serebrennikov Central Ukrainian National Technical University image/svg+xml

DOI:

https://doi.org/10.31548/energiya2(66).2023.071

Abstract

The assessment of the discharge strength of the insulation is of the utmost importance for the prevention of overlap and the establishment of the deadline for the implementation of preventive measures.

Preventive measures used in electric networks to prevent insulator overlap have low efficiency, and existing diagnostic and control tools are not always able to correctly assess the insulating capacity of insulators during operation.

The main reasons for overlapping and damage to the insulation are its contamination with various chemical substances, which is also accompanied by moisture.

Overlapping of the surface of the insulators leads to single-phase short circuits to the ground or to interphase short circuits. The greatest danger is caused by short-circuits accompanied by an intermittent electric arc, which can cause large overvoltages in the electrical network, and their value reaches 3...3.2Uf. Such conditions, in turn, are very favorable for covering the surfaces of insulators.

The non-destructive control method of assessing the insulating capacity of insulators based on the measured values of leakage currents is the most suitable not only for insulators of complete switchgears of 10 kV, but also for external insulation of open switchgears of 35 kV, as it allows continuous automatic control of the degree of contamination of the insulator.

The purpose of the research is to establish the functional dependence between the leakage current of the contaminated insulator and its discharge voltage.

As a result of theoretical studies of the working conditions of insulation during operation, the characteristics of the surface layer of insulators contaminated in natural conditions were determined, these characteristics were analyzed depending on the location of the substation and the time elapsed since the last cleaning. According to the methods of regression and correlation analysis, based on experimental data, an empirical regression line was constructed, which made it possible to determine the insulator leakage current, which is dangerous from the point of view of overlapping.

Key words: support insulator, leakage current, discharge voltage, ground fault

References

Kotysh, A. I. (2001). Avtomatyzovani zasoby tekhnichnoi diahnostyky ta elektrychnoho kontroliu za stanom izoliatsii v silskykh elektrychnykh merezhakh [Automated means of technical diagnostics and electrical control of the state of insulation in rural electrical networks]: Avtoref. dys... k-ta tekhn. nauk: 05.11.13 /NTU “KhPI” Kharkiv, 17.

Gataullin, А. М., Gubaev, D. F. (2022). Integrated Method of Assessment the Type of Damages, their Localization and Predicting the Destruction of High-Voltage Electrical Equipment Insulators by the Partial Discharges Characteristics. Problemele Energetiii Regionale, 1 (53), 152-160.

Kotysh, A. I. (2004). Doslidzhennia protsesiv poverkhnevoho perekryttia opornykh izoliatoriv 10-35 kV v funktsii strumu vytoku [Study of processes of surface overlap of support insulators 10-35 kV as a function of leakage current]. Visnyk NTU "KhPI", Tem. vyp. Elektroenerhetyka i peretvoriuiucha tekhnika. Kharkiv: NTU "KhPI", 7, 133–138.

Serebrennikov, S. V., Sirikov, O. I. (2006). Vybir informatyvnykh parametriv dlia kontroliu zabrudnenosti vysokovoltnykh izoliatoriv [Selection of informative parameters for monitoring contamination of high-voltage insulators]. Fizychni metody ta zasoby kontroliu seredovyshch, materialiv ta vyrobiv, 11: Elektromahnitnyi, ultrazvukovyi ta optychnyi neruinivnyi kontrol materialiv: Zb. nauk. prats. Lviv: Fizyko-mekhanichnyi instytut im. H.V. Karpenka NAN Ukrainy, 224-229.

Serebrennikov, S. V., Sirikov, O. I. (2008). Modeliuvannia kompleksnoho poverkhnevoho strumu vytoku vysokovoltnykh izoliatoriv z urakhuvanniam nerivnomirnosti zabrudnennia poverkhni [Modeling of the complex surface leakage current of high-voltage insulators taking into account the uneven surface contamination]. Visnyk natsionalnoho tekhnichnoho universytetu „Kharkivskyi politekhnichnyi instytut”: Zb. nauk. prats. Kharkiv, 40, 111-114.

Orlovych, A. Iu., Kotysh, A. I., Serebrennikov, S. V. (2000). Avtomatyzovana systema kontroliu za stanom izoliatsii v povitrianykh merezhakh napruhoiu 10-35 kV [Automated system for monitoring the state of insulation in overhead networks with a voltage of 10-35 kV]. Tekhnichna diahnostyka ta neruinivnyi kontrol, 4, 62-65.

Orlovich, A. E., Kotysh, A. I. (1998). Upravleniye avtomatizirovannym obogrevom KRUN na osnove prognoza vypadeniya rosy na izolyatore [Control of automated heating KRUN based on the forecast of dew on the insulator]. Energetika i elektrifikatsiya, 6, 46-48.

Tareev, B. M. (1973). Fizika dielektricheskikh materialov [Physics of dielectric materials]. Moskow: Energiya, 328.

Nerpin, E. B.. Chudnovskiy, L. V. (1967). Fizika pochvy [Soil physics]. Moskow: Nauka, 584.

Brzhezytskyi, V. O., Isakova, A. V., Rudakov, V. V. (2005). Tekhnika i elektrofizyka vysokykh napruh [Technology and electrophysics of high voltages]. Kharkiv : NTU «KhPI», Tornado, 930.

HOST 10390-86 Elektroobladnannia na napruhu ponad 3 kV. Metody vyprobuvan zovnishnoi izoliatsii v zabrudnenomu stani [GOST 10390-86 Electrical equipment for voltage over 3 kV. Methods of testing external insulation in a contaminated state].

Published

2023-05-28

Issue

Section

Статті