Justification of the selection of protection systems for low- and medium-power induction motors based on economic indicators of emergency failures
DOI:
https://doi.org/10.31548/energiya5(87).2026.202Keywords:
induction motor, protection system, diagnostics, turn-to-turn short circuit, reliability indicators, availability factor, economic losses, payback periodAbstract
Low-power (up to 0.75–1 kW) and medium-power (up to 100 kW) induction motors (IMs) are the most widely used electrical machines in the world. Conventional protection devices respond when monitored parameters exceed their settings and disconnect the motor instantly, which leads to increased economic losses. The cost of modern integrated diagnostic and protection systems for IMs is comparable to the cost of the motor itself and is often used as a reason for not applying them, whereas emergency failures of IMs result in significant economic losses. The absence of a unified methodology for selecting protection systems makes it impossible to assess the feasibility of introducing early diagnostic and protection systems for IMs. This paper considers a methodology for selecting diagnostic and protection systems for low- and medium-power IMs taking reliability indicators into account. Based on international survey data, it is shown that IM downtime is determined by the combined effect of two factors: the industry (field) of application and the power and speed class. In economic terms, the introduction of a method for early functional detection of turn-to-turn short circuits reproduces the effect of systematic "excellent" maintenance (short downtime per event) without physically stopping the motor for inspection. This is confirmed both by classical IEEE surveys and by recent industry data on the effectiveness of continuous diagnostic monitoring (a 70–75% reduction in unplanned failures). The economic effect of reducing downtime scales primarily with the criticality of the technological process rather than with the motor power: for the 4A80A2U3 motor, eliminating 36 h/year of emergency downtime yields annual savings ranging from approximately UAH 13 thousand to more than UAH 800 thousand, depending on the technological cycle in which the motor is used
Received: 28.08.2026. Revised: 02.10.2026. Accepted: 16.10.2026References
1. Ostashevskyi, M. O., & Yurieva, O. Yu. (2017). Elektrychni mashyny i transformatory [Electrical machines and transformers] (V. I. Milykh, Ed.). Kharkiv: FOP Panov A. M.
2. Nandi, S., Toliyat, H. A., & Li, X. (2005). Condition monitoring and fault diagnosis of electrical motors – A review. IEEE Transactions on Energy Conversion, 20(4), 719–729.
3. Henao, H., et al. (2014). Trends in fault diagnosis for electrical machines: A review of diagnostic techniques. IEEE Industrial Electronics Magazine, 8(2), 31–42.
4. Shullie, Yu. A., & Pedos, T. Z. (2023). Otsiniuvannia zbytkiv pidpryiemstv vid porushennia elektropostachannia [Assessment of enterprise losses caused by power supply interruptions] (Candidate’s dissertation). Vinnytsia National Technical University, Vinnytsia.
5. Ruvin, O. H. (2014). Rozrobka ekspertnykh metodyk: zmist, struktura, oformlennia (z urakhuvanniam mizhnarodnykh standartiv system upravlinnia yakistiu, adaptovanykh v Ukraini) [Development of expert methodologies: Content, structure, and design (considering international quality management standards adapted in Ukraine)]. Kyiv: KNDISE.
6. Pozdniakov, Yu. V., Skybinska, Z. M., & Hryniv, T. T. (2020). Analitychne obgruntuvannia metodyky rozrakhunku pokaznykiv nevyznachenosti rezultatu nezalezhnoi otsinky vartosti aktyviv [Analytical justification of the methodology for calculating uncertainty indicators of independent asset valuation results]. Visnyk Odeskoho natsionalnoho universytetu. Ekonomika, 25(1), 80–85.
7. Pozdnyakov, Y., & Bratishko, I. (2022). Challenging issues of performing forensic economic examinations of reports on independent expert valuation of asset value. Theory and Practice of Forensic Science and Criminalistics, 26(1), 108–124.
8. Kryvonosov, V., Kryvonosov, V., & Prokopenko, S. (2026). Potential loss as a criterion for the selection of electrical equipment diagnostic and protection systems. Energy and Automation, 2(84), 77–84. https://doi.org/10.31548/energiya2(84).2026.077
9. Kryvonosov, V. Ye., Antypov, Ye. O., Kryvonosov, V. V., & Prokopenko, S. O. (2026). Sposib vyiavlennia vytkovoho zamykannia v obmotkakh elektrodvyhuna, pratsiuiuchoho v umovakh vypadkovykh zmin parametriv merezhi zhyvlennia ta navantazhen na valu [Method for detecting turn-to-turn faults in motor windings operating under random variations of supply network parameters and shaft loads] (Patent of Ukraine No. 163792). https://sis.nipo.gov.ua/uk/search/detail/1941122/
10. Kryvonosov, V. Ye., Antypov, Ye. O., Kryvonosov, V. V., & Prokopenko, S. O. (2026). Sposib vyiavlennia vytkovoho zamykannia v statornykh obmotkakh elektrodvyhuna, shcho pratsiuie pry nestatsionarnykh rezhymakh napruhy ta navantazhennia [Method for detecting turn-to-turn faults in motor stator windings operating under non-stationary voltage and load conditions] (Patent of Ukraine No. 164091). https://sis.nipo.gov.ua/uk/search/detail/1936105/
11. DSTU 2860-94. (1994). Nadiinist tekhniky. Terminy ta vyznachennia [Reliability of equipment. Terms and definitions]. Kyiv: Derzhstandart Ukrainy.
12. Pravyla ulashtuvannia elektroustanovok [Electrical installation rules]. (2017). Kyiv: Ministry of Regional Development, Construction and Housing and Communal Services of Ukraine.
13. Bonnett, A. H., & Soukup, G. C. (1992). Cause and analysis of stator and rotor failures in three-phase squirrel-cage induction motors. IEEE Transactions on Industry Applications, 28(4), 921–937. https://doi.org/10.1109/28.148460
14. Albrecht, P. F., Appiarius, J. C., McCoy, R. M., Owen, E. L., & Sharma, D. K. (1986). Assessment of the reliability of motors in utility applications. IEEE Transactions on Energy Conversion, EC-1(1).
15. Penrose, H. W. (2025). What the large motor reliability studies actually found and why it matters. ReliaMag. https://reliamag.com/articles/large-motor-reliability-studies/
16. Levitt, J. (2026). The real cost of unplanned downtime in manufacturing (2026 data). ReliaMag. https://reliamag.com/articles/cost-unplanned-downtime-manufacturing/
17. ABB. (2025, October 14). Industrial downtime costs up to $500,000 per hour and can happen every week [Press release]. https://new.abb.com/news/detail/129763/
18. Thorsen, O. V., & Dalva, M. (1995). A survey of faults on induction motors in offshore oil industry, petrochemical industry, gas terminals, and oil refineries. IEEE Transactions on Industry Applications, 31(5), 1186–1196.
19. Syvokobylenko, V. F., & Tkachenko, S. M. (2020). Metodyka eksperymentalnoho vyznachennia parametriv skhem zamishchennia asynkhronnykh dvyhuniv [Methodology for experimental determination of the equivalent circuit parameters of induction motors]. Elektrotekhnika i elektromekhanika, (4), 15–22.
20. Huk, M. Yu. (2011). Nadiinist elektroenerhetychnykh system [Reliability of electric power systems]. Lviv: Vydavnytstvo Lvivskoi politekhniky.
21. Chornovil, O. P., & Leshchenko, I. T. (2006). Nadiinist elektroobladnannia promyslovykh pidpryiemstv [Reliability of electrical equipment of industrial enterprises]. Kyiv: NTUU "KPI".
22. IEEE. (2007). IEEE recommended practice for the design of reliable industrial and commercial power systems (IEEE Std 493-2007, Gold Book). New York: IEEE.
Published
Issue
Section
License
Copyright (c) 2026 Energy and Automation

This work is licensed under a Creative Commons Attribution-NonCommercial 4.0 International License.
All materials are disseminated under the terms of the Creative Commons Attribution 4.0 International Public License, which permits others to distribute the manuscript with proper acknowledgement of the authorship and the original publication in this journal.